Pasia Industries Ltd

PASIA INDUSTRIES LTD ————​Leading MI Cable Heating

Manufacturer from China
Active Member
5 Years
Home / Products / Mineral Insulated Heating Cable /

300V 825 Sheath Mineral Insulated Heating Cable

Contact Now
Pasia Industries Ltd
Province/State:zhejiang
Country/Region:china
Contact Person:Warren Sun
Contact Now

300V 825 Sheath Mineral Insulated Heating Cable

Ask Latest Price
Video Channel
Brand Name :MICH
Model Number :300R825ASMIHCTC
Certification :ISO9001
Place of Origin :China
MOQ :1 meter
Price :USD0.5-USD5 per meter
Payment Terms :L/C, T/T
Supply Ability :20 million meters
Delivery Time :in one month
Packaging Details :plywood crates
Sheath :825 Alloy Sheathed
Function :Heating or Heat Trace
Application :Harsh Environment and corrosion resistance
Diameter :up to 5.2 mm
Cable Length :in Meter
Power :in Watt
Votage :300 Volt
Unit Weight :Up to 184 kg/km
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

300V Rated 825 Alloy Sheath Mineral Insulated Heating Cable of Two Cores is a special mineral insulated heating cable of 825 Alloy Sheath with two conductors inside the cable to be connected with the 300 V voltage power supply.

Heating Cable Specification (300V Double Cores)

Cable Code Diameter Nominal resistance at +20 Maximum manufacturing length Unit weight
mm Ω/m m kg/km
23K210 5.2 0.21 222 117.9
23K300 4.8 0.3 261 98.9
23K400 4.8 0.4 261 97.2
23K480 4.8 0.48 261 96.0
23K650 4.6 0.65 284 87.3
23K1000 4.1 1.0 100 68.9
23K1300 3.8 1.3 100 58.9
23K2000 5.0 2.0 100 104.7
23K2400 4.8 2.4 100 95.7
23K3000 4.6 3.0 100 87.3
23N4600 4.8 4.6 100 96.3
23N7500 4.6 7.5 100 86.9
23N11200 4.4 11.2 100 78.7
23N14000 4.2 14.0 100 71.6
23N18000 3.6 18.0 100 52.6
23N26000 3.6 26.0 100 52.2
23N40000 3.4 40.0 100 46.4
23N50000 4.0 50.0 100 63.8
23N60000 3.6 60.0 100 51.7
23N72000 3.4 72.0 100 46.1

Note: the resistance value of 2-core cable in the above table is the measured value after the ends are twisted (i.e., single-core resistance X2);

For the use of 660V voltage occasions, please contact our company professionals.

Table 5 terminal specifications

Cable Structure

300V 825 Sheath Mineral Insulated Heating Cable

Application

High temperature pipeline heat tracing Anti-coagulation and viscosity decreasing for process media
Tank/vessel heating Metal manufacturing industry -- low melting point alloy melting
Extruder shell heating Recycling of nuclear fuel waste
All kinds of industrial electric heaters

Specification

Heating cable instruction code

MI AL-B 16K6560/60/2520/220/E1

No. 1 2 3 4 5 6 7

No. Instruction
1 Sheath material 825 alloy
2 structure of cable components shown in table 1
3 cable codes shown in table 2, 3 and 4
4 length of heating cable In meter
5 Heating cable power In Watt
6 heating cable voltage In Volt
7 heating cable voltage See table 5

Cable Code

1 6 K 6560

No. 1 2 3 4

Serial NO. Instruction
1 core number 1 or 2
2 Voltage grade 3=300V, 6=600V
3 conductor materials K,N,C
4 cold resistance ×1000 6560=6.56Ω/m×1000

Table 1 Structure of Cable Element

300V 825 Sheath Mineral Insulated Heating Cable

Inquiry Cart 0