Add to Cart
Heating Cable Specification (300V Double Cores)
Cable Code | Diameter | Nominal resistance at +20℃ | Maximum manufacturing length | Unit weight |
mm | Ω/m | m | kg/km | |
23K210 | 5.2 | 0.21 | 222 | 117.9 |
23K300 | 4.8 | 0.3 | 261 | 98.9 |
23K400 | 4.8 | 0.4 | 261 | 97.2 |
23K480 | 4.8 | 0.48 | 261 | 96.0 |
23K650 | 4.6 | 0.65 | 284 | 87.3 |
23K1000 | 4.1 | 1.0 | 100 | 68.9 |
23K1300 | 3.8 | 1.3 | 100 | 58.9 |
23K2000 | 5.0 | 2.0 | 100 | 104.7 |
23K2400 | 4.8 | 2.4 | 100 | 95.7 |
23K3000 | 4.6 | 3.0 | 100 | 87.3 |
23N4600 | 4.8 | 4.6 | 100 | 96.3 |
23N7500 | 4.6 | 7.5 | 100 | 86.9 |
23N11200 | 4.4 | 11.2 | 100 | 78.7 |
23N14000 | 4.2 | 14.0 | 100 | 71.6 |
23N18000 | 3.6 | 18.0 | 100 | 52.6 |
23N26000 | 3.6 | 26.0 | 100 | 52.2 |
23N40000 | 3.4 | 40.0 | 100 | 46.4 |
23N50000 | 4.0 | 50.0 | 100 | 63.8 |
23N60000 | 3.6 | 60.0 | 100 | 51.7 |
23N72000 | 3.4 | 72.0 | 100 | 46.1 |
Note: the resistance value of 2-core cable in the above table is the measured value after the ends are twisted (i.e., single-core resistance X2);
For the use of 660V voltage occasions, please contact our company professionals.
Application
High temperature pipeline heat tracing | Anti-coagulation and viscosity decreasing for process media |
Tank/vessel heating | Metal manufacturing industry -- low melting point alloy melting |
Extruder shell heating | Recycling of nuclear fuel waste |
All kinds of industrial electric heaters |
Specification
Heating cable instruction code
MI AL-B 16K6560/60/2520/220/E1
No. 1 2 3 4 5 6 7
No. | Instruction | |
1 | Sheath material | 825 alloy |
2 | structure of cable components | shown in table 1 |
3 | cable codes | shown in table 2, 3 and 4 |
4 | length of heating cable | In meter |
5 | Heating cable power | In Watt |
6 | heating cable voltage | In Volt |
7 | heating cable voltage | See table 5 |
Cable Code
1 6 K 6560
No. 1 2 3 4
Serial NO. | Instruction | |
1 | core number | 1 or 2 |
2 | Voltage grade | 3=300V, 6=600V |
3 | conductor materials | K,N,C |
4 | cold resistance ×1000 | 6560=6.56Ω/m×1000 |
Cable Structure
Structure of Cable Element
Terminal specifications
Model: A, D, E | Model: B | |||
Maximum Voltage(V) | Maximum Current (A) | Terminal Specification | Maximum Current (A) | Terminal Specification |
600 | 15 | E2 | 20 | E1 |
600 | 20 | E2 | 25 | E2 |
600 | 30 | E3 | 40 | E2 |
600 | 50 | E3 | 70 | E2 |
600 | 70 | E3 | 100 | E3 |
Note 1: E1 means 1/2 "NPT;E2 means 3/4 "NPT;E3 represents 1 "NPT (taper thread);Additional connection thread requirements are available.
Note 2: the length of cold end cable with standard configuration is 2 meters. If you increase or decrease of length required, please contact our professional personnel.
Corresponding reference table between the output power and sheath temperature
Anticorrosive specification
Material | ||
Sulfate | good | |
Hydrochloric acid | good | |
Hydrofluoric acid | good | |
Phosphate | good | |
Carbonate | good | |
Organic acid | good | |
Alkali metal | good | |
Sea water | good | |
Chloride | good |
Explosion-proof instructions
MIAL series heating cable with explosion-proof terminal, can be used in potential explosive environment. Authenticated by the Chinese CQST, in accordance with Chinese GB3836 explosion-proof electrical standards, they can be applicable to Ⅱ A, Ⅱ B, Ⅱ C (C1D2) level of explosion-proof electrical equipment.